Drilling, workover and well service equipment · Baoji, Shanxi, China
info@bomcochina.com Service centres: UAE · Kuwait · Oman · Saudi Arabia · Egypt
Power Equipment

GCS Drawout Switchgear

Drawout assembly for plants that interface with a control system: 50/60 Hz, AC 380 or 660 V, up to 4,000 A, single or double busbar form.

Specification Factory ratings, dimensions and masses are tabulated below, translated from the manufacturer's data sheet.

Request data sheet →

Specifications

Factory data

GCS adds a 2,500 V dielectric test, 4,000 A horizontal busbars and a 200 kW motor rating for the same draw-out format.

Main circuit rated voltage
AC 380 V (660 V)
Auxiliary circuit rated voltage
AC 220 V (380 V); DC 110 / 220 V
Rated frequency
50 Hz (60 Hz)
Rated insulation voltage
660 V
Dielectric withstand voltage
2,500 V
Horizontal busbar rated current
1,600 / 2,500 / 3,150 / 4,000 A
Vertical busbar rated current
1,000 A
Busbar short-time withstand current (rms)
50 / 80 kA (1 s)
Busbar peak withstand current
105 / 176 kA (0.1 s)
Feeder short-circuit breaking current (rms)
50 kA (1 s)
Main circuit plug-in connector
200 / 400 A
Auxiliary circuit plug-in connector
15 A
Maximum motor rating
200 kW
Degree of protection
IP30 / IP40
Operating mode
Local / remote / automatic

Translated from the GCS Drawout Switchgear datasheet issued by BOMCO. Figures are factory values in SI units; the quotation confirms the exact build for your order.

How we supply it

We build GCS Drawout Switchgear in Baoji and test each unit against the figures above before it leaves the works. Our engineers set the rating point at commissioning to suit your fuel, altitude and ambient conditions, and we hand over the signed test sheet with the unit.

Tell us the duty you have in mind for GCS Drawout Switchgear and we will confirm which row of the table applies, or quote a special build when none of them fits.

Design details

How we build this unit

Application notes

Where it earns its place

Power distribution centre and motor control centre in one lineup. That is the detail a catalogue listing usually leaves out, and the one that decides whether the unit suits the well in front of you.

Plants that talk to a supervisory system need drawout gear with a clean interface, which is what the GCS build provides.

Send the well programme →

GCS Drawout Switchgear detail view
Supply notes

How this unit is specified and shipped

The GCS low voltage drawout switchgear is built for plants that interface with a control system: 380 or 660 V, up to 4,000 A, single or double busbar.

Equipment this unit runs with

Other power equipment models

Four Cylinder Marine Diesel Engine

Four Cylinder Marine Diesel Engine

190 Series Diesel Engines

Inline Land Diesel Engine

Inline Land Diesel Engine

190 Series Diesel Engines

Ask for a data sheet on GCS Drawout Switchgear

Request a Quote →
BOMCO
Request a Quote