Factory data

GCK is the draw-out low-voltage assembly for plant distribution: 660 V insulation, main busbars to 4,000 A and IP30/IP40 enclosures.

Rated insulation voltage
660 V
Rated working voltage
380 / 660 V
Auxiliary circuit rated voltage
AC 380 V (660 V)
Main busbar rated current
1,000 / 1,250 / 1,600 / 2,000 / 2,500 / 4,000 A
Main busbar short-time withstand current
50 kA (1 s)
Main busbar peak withstand current
105 kA
Branch busbar rated current
1,000 A
Branch busbar short-time withstand current
50 kA (1 s)
Branch busbar peak withstand current
105 kA
Degree of protection
IP30 / IP40

Translated from the GCK Drawout Switchgear datasheet issued by BOMCO. Figures are factory values in SI units; the quotation confirms the exact build for your order.

How we supply it

We build GCK Drawout Switchgear in Baoji and test each unit against the figures above before it leaves the works. Our engineers set the rating point at commissioning to suit your fuel, altitude and ambient conditions, and we hand over the signed test sheet with the unit.

Tell us the duty you have in mind for GCK Drawout Switchgear and we will confirm which row of the table applies, or quote a special build when none of them fits.

Design details

How we build this unit

Application notes

Where it earns its place

Power centre, motor control centre and compensation cabinets. That is the detail a catalogue listing usually leaves out, and the one that decides whether the unit suits the well in front of you.

For 660 V plant distribution the GCK lineup covers power, motor control and compensation from one family.

Send the well programme →

GCK Drawout Switchgear detail view
Supply notes

How this unit is specified and shipped

The GCK switchgear is a drawout assembly for distribution, motor control, capacitor compensation and lighting boards in plants up to 660 V.

Equipment this unit runs with

Other power equipment models

Eight Cylinder Marine Diesel Engine

Eight Cylinder Marine Diesel Engine

190 Series Diesel Engines

Four Cylinder Marine Diesel Engine

Four Cylinder Marine Diesel Engine

190 Series Diesel Engines

Inline Land Diesel Engine

Inline Land Diesel Engine

190 Series Diesel Engines

Ask for a data sheet on GCK Drawout Switchgear

Request a Quote →
BOMCO
Request a Quote